Loadbuster Disconnect

Loadbuster Disconnects®

Loadbuster Disconnects, when used with Loadbuster® Tool, S&C’s portable loadbreak tool, provide the ultimate in low-cost, universal live switching. They offer the operating flexibility of a system with multipoint interrupter switches . . . without the cost associated with building an interrupter into every switch.

S&C’s Loadbuster Disconnects are manufactured in accordance with a quality system certified to ISO9001:2000.

 

 

 

Features

Loadbuster Disconnects are:

  • Unexcelled as a straight disconnect: With their rugged station-type reliability, they accommodate the prevailing heavier loads and higher fault currents.
  • When used with Loadbuster, they not only can switch load currents through 900 amperes at distribution voltages up to 34.5 kV, but can also break associated transformer-magnetizing currents, line-charging currents, and cable-charging currents.
  • Loadbuster Disconnects—Overhead Pole-Top Style are also available with composite-polymer silicone insulators.

Ratings

 

Branch Feeder, Main Feeder, Crossarm, and Station Styles
50/60-Hz Ratings Disconnect
Gap
kV Amperes, RMS
Nom. Max BIL Cont. Mom.,
Asym.
Inches mm
14.4 15.5 110 600 40 000 8 203
10-7/8 276
10 254
900 40 000 7-1/2 191
10 254
25 27 125 600 40 000 10-7/8 276
900 40 000 10-1/2 267
25/34.5 38 150 600 40 000 10 254
900 40 000 14 356
34.5 38 150 900 40 000 14 356
200 900 40 000 14 356

 

Overhead Pole-Top Style
50/60-Hz Ratings Disconnect
Gap
kV Amperes, RMS
Nom. Max BIL Cont. Mom.,
Asym.
Inches mm
14.4 15.5 110 900Triangle 36 000 8 203
25 27 150 900Triangle 36 000 11 279
34.5 38 170Square 900Triangle 36 000 11 279

Square S&C’s tested value. Rating per ANSI: 150 kV.
Triangle S&C’s certified value. Rating per ANSI: 600A.

Operation

1. Attach

Attaching Loadbuster Tool.

Reach across the front of the disconnect and attach Loadbuster’s anchor to the attachment hook on the far side of the device. Then engage its pull ring with Loadbuster’s pull-ring hook. Loadbuster’s pull-ring latch prevents inadvertent disengagement of the disconnect pull ring and Loadbuster’s pull-ring hook.

2. Pull

Pulling Loadbuster Tool downward.

A firm, steady downward pull on Loadbuster — to its maximum extended length — opens the disconnect in the normal manner as the current is diverted through Loadbuster. At a predetermined point in the opening stroke, Loadbuster trips, breaking the circuit positively.

3. Remove

Removing Loadbuster Tool.

Loadbuster is disengaged by first removing its anchor from the disconnect attachment hook. Then, with the blade in the open position, Loadbuster is removed from the pull ring with a simple “roll-off” motion.

Styles

Branch Feeder Inverted Style

Branch Feeder Inverted Style

Branch Feeder Vertical Style

Branch Feeder Vertical Style

Main Feeder Style

Main Feeder Style

Station Vertical Style

Station Vertical Style

Crossarm Inverted Style

Crossarm Inverted Style

Crossarm Vertical Style

Crossarm Vertical Style