| kV | Amperes, RMS | ||||||
|---|---|---|---|---|---|---|---|
| System Class |
Max | BIL | Main Bus | Load-Interrupter Switch Continuous & Load Dropping |
Fault Interrupter |
Short-Circuit (Sym.) |
|
| Continuous & Load Dropping |
Interr. (Sym.) |
||||||
| 15.5 (12) | 15.5 (15.5) | 95 (95) | Up to 2000 (2000) |
600 (630) |
600 (630) |
Up to 25 000 (25 000) |
Up to 25 000 (25 000) |
| 27 (24) | 29 (29) | 125 (125) | |||||
| 38 (36) | 38 (38) | 150 (150) | |||||
| 15.5 (12) | 15.5 (15.5) | 95 (95) | Up to 2000 (2000) |
900 (900) |
900 (900) |
25 000 (25 000) |
25 000 (25 000) |
| 27 (24) | 29 (29) | 125 (125) | |||||
| 38 (36) | 38 (38) | 150 (150) | |||||