Mark V Circuit-Switchers are especially suited for switching and protection of shunt capacitor banks. They can be fitted with optional pre-insertion inductors to minimize capacitor-bank switching transients, markedly improving power quality.
Mark V Circuit-Switcher employs an in-series circuit-breaking interrupter and a circuit-making and isolating disconnect, making it especially suited for switching and protection of transformers, lines, cables, capacitor banks, and line-connected or tertiary-connected shunt reactors. Mark V Circuit-Switcher is available in three styles — Vertical-Break, Center-Break, and Integer.
RELATED ARTICLES
Performance-proven through over 40 years of reliable service
For more information regarding transient control, refer to the technical paper titled “Selecting a Capacitor-Switching Overvoltage Control Method Effective in Preventing Nuisance Tripping of Adjustable-Speed Drives”.
Mark V Circuit-Switchers are also well-suited for transformer, line, cable, and reactor switching and protection. For more information, see S&C Specification Bulletin 711-31.
| kV | Amperes, RMS | |||||
|---|---|---|---|---|---|---|
| Nom. | Max | BIL | Cont. | Short-Time | Fault-Closing, Duty-Cycle, One-Time |
|
| Mom. | 3-Second | |||||
| 34.5 | 38 | 200 | 1200 | 61 000 | 40 000 | 30 000 |
| 46 | 48.3 | 250 | 1200 | 61 000 | 40 000 | 30 000 |
| 69 | 72.5 | 350 | 1200 | 61 000 | 40 000 | 30 000 |
| 115 | 121 | 550 | 1200 | 61 000 | 40 000 | 30 000 |
| 138 | 145 | 650 | 1200 | 61 000 | 40 000 | 30 000 |
| 161 | 169 | 750 | 1200 | 61 000 | 40 000 | 30 000 |
| 230 | 242 | 900 | 1600 | 70 000 | 43 750 | 40 000 |
| 2000 | 80 000 | 50 000 | 40 000 | |||
| 345 | 362 | 1300 | 1600 | 70 000 | 43 750 | 40 000 |
| 2000 | 80 000 | 50 000 | 40 000 | |||
| Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
|---|---|---|
| Parallel Switching | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000 |
| Load Dropping and Magnetizing Current Switching | Transformers connected to solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000 |
| All other connections of transformers | 1200/1600/2000 |
|
| Fault Interrupting | Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than |
7000 or 8000 |
| Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher less than |
4000 (3000A for 115-kV single-gap Circuit-Switchers) | |
| Secondary faults all other connections of transformers | 4000 (3000A for 115-kV single-gap Circuit-Switchers) | |
| Internal faults see both primary and secondary faults, above | ||
Depending on continuous rating of Circuit-Switcher.
Will switch magnetizing currents associated with such loads.
Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
| System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
|---|---|---|---|---|---|
| Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
| Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
|---|---|---|
| Load Splitting (Parallel or Loop Switching) | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000 |
| Load Dropping | Circuits with all load-side transformers connected solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000 |
| Circuits with all load-side transformers connected other than as described above. | 1200/1600/2000 |
|
| Line Dropping | Maximum length of line: 300 miles. | |
| Fault Interrupting | Line or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than |
7000 or 8000 |
| Line or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher less than |
4000 (3000A for 115-kV single-gap Circuit-Switchers) | |
Depending on continuous rating of Circuit-Switcher.
Total connected length of all ovehead lines (in all directions)
including any number of feeders connected to source-side substations as indicated in the table below:
| System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
|---|---|---|---|---|---|
| Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
| Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
|---|---|---|
| Load Splitting (Parallel or Loop Switching) | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000 |
| Load Dropping | Circuits with all load-side transformers connected solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000 |
| Circuits with all load-side transformers connected other than as described above. | 1200/1600/2000 |
|
| Cable Dropping (Charging Current) | Shielded and Unshielded Cable | 550 |
| Fault Interrupting | Cable or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher not less
than |
7000 or 8000 |
| Cable or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher less than |
4000 (3000A for 115-kV single-gap Circuit-Switchers) |
Depending on continuous rating of Circuit-Switcher.
Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
| System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
|---|---|---|---|---|---|
| Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
| Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
|
|---|---|---|---|
| Bank Current Switching | Grounded capacitor bank | Applications on solidly grounded systems through 69 kV | 1000 |
| All other applications | 550 | ||
| Ungrounded capacitor bank | 550 | ||
| Fault Interrupting | Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than |
7000 or 8000 | |
| Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher less than |
4000 (3000A for 115-kV single-gap Circuit-Switchers) | ||
Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
| System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
|---|---|---|---|---|---|
| Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
| Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
|
|---|---|---|---|
| Series Reactor Switching | Refer to the nearest S&C Sales Office. | ||
| Shunt Reactor Switching and Protection (Line-Connected or Tertiary Connected Reactors) | Reactor Current Switching | Reactor wye-connected with solidly grounded neutral | 1000 |
| Reactor delta-connected, or wye-connected with ungrounded neutral | 1000 | ||
| Fault Interrupting | Oil-insulated reactors | 2800 | |
| Air-insulated reactors | 2000 | ||
Pre-insertion inductors are especially suited for limiting transient overvoltages which, through voltage manification, can result in nuisance tripping of adjustable-speed drives and other sensitive electronic devices. Voltage magnification can occur where power-factor correction capacitors and/or voltage control capacitors are applied on the utility distribution system or on a utility customer’s low voltage bus, and is caused by a near-resonant condition between the switched capacitor bus and the capacitances at lower voltages.
Pre-insertion inductors are more effective than controlled-closing schemes and pre-insertion resistors for limitation of:
How does the pre-insertion inductor work?
First, an open-air arc makes up the initial circuit through the pre-insertion inductor. The inductor core picks up the inrush current before it reaches the main contact. Then, the pre-insertion inductor is bypassed, and disconnected as the moving arcing rod rotates. As the main contact is made, the pre-insertion inductor is completely removed from the circuit. Let's take a look at it in action:
The sliding contact arrangement places the pre-insertion inductor in the circuit for only a few cycles. That’s how long it takes to provide high-quality transient control.
For complete application information on S&C Pre-insertion Inductors refer to S&C Data Bulletin 711-95 or contact the nearest S&C Sales Office.
The Type CS-1A Switch Operator direct-drives the vertical-break disconnect of the Mark V Circuit-Switcher. It provides trip-free capability. Should the Mark V be inadvertently closed into a fault sensed by user-furnished relays, Mark V will trip immediately.
The operator features a sturdy welded enclosure with baffled louvers that allow air circulation, but keep out rain. The interior of the weatherproof, dustproof enclosure is accessed by a hinged door . . . rather than removal of the entire enclosure.
The Type CS-1A Switch Operator includes:
Optional features for the Type CS-1A Switch Operator include: