Mark V Circuit-Switchers
Ratings
| kV | Amperes, RMS | |||||
|---|---|---|---|---|---|---|
| Nom. | Max | BIL | Cont. | Short-Time | Fault-Closing, Duty-Cycle, One-Time |
|
| Mom. | 3-Second | |||||
| 34.5 | 38 | 200 | 1200 | 61 000 | 40 000 | 30 000 |
| 46 | 48.3 | 250 | 1200 | 61 000 | 40 000 | 30 000 |
| 69 | 72.5 | 350 | 1200 | 61 000 | 40 000 | 30 000 |
| 115 | 121 | 550 | 1200 | 61 000 | 40 000 | 30 000 |
| 138 | 145 | 650 | 1200 | 61 000 | 40 000 | 30 000 |
| 161 | 169 | 750 | 1200 | 61 000 | 40 000 | 30 000 |
| 230 | 242 | 900 | 1600 | 70 000 | 43 750 | 40 000 |
| 2000 | 80 000 | 50 000 | 40 000 | |||
| 345 | 362 | 1300 | 1600 | 70 000 | 43 750 | 40 000 |
| 2000 | 80 000 | 50 000 | 40 000 | |||