Three-Pole Side-Break Integer Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
14.4 17.0 110 600 40 000
25 27 150 600 40 000
25/34.5 38 150 600 40 000
34.5 38 200 600 40 000

 

Three-Pole Vertical-Break Integer Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
34.5 38 200 600 40 000
34.5 38 200 1200 40 000

 

Three-Pole Double-Break Integer Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
46 48.3 250 600 40 000

 

Three-Pole Side-Break Heavy-Duty Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
14.4 17.0 110 600 40 000
25 27 150 600 40 000
34.5 38 200 600 40 000

 

Three-Pole Vertical-Break Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
14.4 17.0 110 600 40 000
14.5 17.0 110 1200 61 000
25 27 150 600 40 000
25/34.5 38 150 1200 40 000
34.5 38 200 600 40 000
34.5 38 200 1200 40 000

 

Three-Pole Double-Break Style (Group Operated)
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
34.5 38 200 600 40 000
46 48.3 250 600 40 000

 

Single-Pole Heavy-Duty Style
50/60-Hz Ratings
kV Amperes, RMS
Nom. Max BIL Continuous and Interrupting Momentary, Asymmetrical
14.4 17.0 110 600 40 000
14.4 17.0 110 1200 61 000
25 27 150 600 40 000
25 27 150 1200 61 000